Skip to main content

FAQ

Rupture panels can add an additional layer of overpressure protection against internal overpressure. Given the propensity of hydrogen to generate higher over-pressures when ignited compared to other fuels, rupture panels are often part of the safety design for containerized systems. The need for a rupture panel for a specific system will be determined by the system hazard analysis and the…

Category: System Design

While not required, Safety Instrumented Systems with a specific SIL rating are often used on hydrogen systems. The hazard analysis provides guidance as to whether a SIL rating for a given exposure is required and at what level. The SIL level depends on the probability and consequence of occurrence of a given hazard. Hydrogen equipment may be provided with different SIL levels within the same…

Category: System Design

Both types of valve actuators are used, and both offer advantages and disadvantages for a given application.

Category: System Design

The containerized electrolysis unit should be installed per manufacturer instructions, the requirements
of its listing such as to ISO 22734, Hydrogen generators using water electrolysis - Industrial, commercial,
and residential applications, and NFPA 2, Hydrogen Technologies Code. A primary consideration for
indoor installation is the potential for hydrogen releases from the system,…

Category: System Design

The suspected cause was a mixture of oxygen and hydrogen that passed downstream from the electrolysis unit into several storage vessels. Hydrogen-oxygen mixtures are very hazardous. Subsequent ignition resulted in internal pressure that exceeded the limits of the storage system. The design of electrolyzers, detection of upset conditions, and preventing the accumulation of oxygen within the…

Category: System Design

Hydrogen has been used as a fuel to operate cars, buses, trucks, submarines, aircraft, forklifts, trains and virtually every type of mobile equipment. Each has special considerations which often drive specific requirements for that vehicle type. For example, higher g-loadings of rail operations and operations within tunnels are a couple considerations, but there are no significant barriers…

Keywords: Train

All systems must be designed for the applicable operating parameters such as pressure, temperature,
and flow. The sub-cooled liquid hydrogen (sLH2) approach for fueling is comparable to other processes
commonly used to handle cryogenic liquids in the industrial gas industry where remaining gas is
condensed during the fill operation. These processes often operate above the critical…

Detection systems are nearly always installed but the system design and installation details of detection equipment are up to the manufacturer. Standards are being developed for this market.

There is no maximum flow-rate that can be vented to the atmosphere, but the hazard analysis should consider the potential risk of dispersion, radiation, and overpressure as part of the vent system design. Flare systems are often used at large hydrogen production facilities as one means to prevent a large unignited cloud from forming but will depend on the specific application.

Category: System Design

The routing will be dependent on the system design, size of release, and evaluation of the hazards.
Smaller systems are rarely vented to a flare due to complexity, availability and permitting considerations.
Facilities handling large amounts of hydrogen such as production plants will often have a flare system
since they have more capability for this additional onsite infrastructure.…

Category: System Design